Article 10-14 BANKS/ATMS

This article is included in your selections.

All fixtures for the ATM or teller areas shall be full-cutoff. The fixtures at drive-up canopies shall be either recessed into the canopy ceiling, or mounted so that the lowest portion of the fixture is higher than the canopy fascia. Maintained average horizontal illuminance at grade under the canopy or adjacent to the ATM shall be calculated separately from the rest of the site and shall not exceed 20.0 footcandles in Zones 1 and 2, and shall not exceed 30.0 footcandles in Zones 3 and 4.